3.0
2018-07-24T08:27:06Z
Templates USV
APC Smart-UPS SNMP Basic
APC Smart-UPS SNMP Basic
Templates USV
Ausgang
Eingang
Information
Umgebung
Verfügbarkeit
-
Batteriespannung
4
{$SNMP_COMMUNITY}
0
.1.3.6.1.4.1.318.1.1.1.2.2.8.0
upsAdvBatteryActualVoltage
30
90
365
0
0
V
0
0
0
0
1
0
0
0
Verfügbarkeit
-
Ausgangslast (%)
4
{$SNMP_COMMUNITY}
0
.1.3.6.1.4.1.318.1.1.1.4.2.3.0
upsAdvOutputLoad
30
7
365
0
0
%
0
0
0
0
1
0
0
0
Ausgang
-
Batterieaustausch notwendig
4
{$SNMP_COMMUNITY}
0
.1.3.6.1.4.1.318.1.1.1.2.2.4.0
upsAdvReplaceBatteryIndicator
600
7
365
0
3
0
0
0
0
1
0
0
0
Verfügbarkeit
APC Battery Replacement Status
-
Verbleibende Laufzeit
4
{$SNMP_COMMUNITY}
1
.1.3.6.1.4.1.318.1.1.1.2.2.3.0
upsAdvRunTimeRemaining
30
7
365
0
3
s
0
0
0
0
0.01
0
0
0
Verfügbarkeit
-
Kalibrierungsdatum
4
{$SNMP_COMMUNITY}
0
1.3.6.1.4.1.318.1.1.1.7.2.7.0
upsAdvTestCalibrationDate
30
90
0
0
2
0
0
0
0
1
0
0
0
Verfügbarkeit
-
Kalibrierung
4
{$SNMP_COMMUNITY}
0
1.3.6.1.4.1.318.1.1.1.7.2.6.0
upsAdvTestCalibrationResults
30
90
365
0
3
0
0
0
0
1
0
0
0
Verfügbarkeit
APC Kalibrierung
-
Letzter Batterietausch
4
{$SNMP_COMMUNITY}
0
1.3.6.1.4.1.318.1.1.1.2.1.3.0
upsBasicBatteryLastReplaceDate
86400
90
0
0
2
0
0
0
0
1
0
0
0
Verfügbarkeit
-
Batterie-Status
4
{$SNMP_COMMUNITY}
0
.1.3.6.1.4.1.318.1.1.1.2.1.1.0
upsBasicBatteryStatus
30
7
365
0
3
0
0
0
0
1
0
0
0
Verfügbarkeit
APC Battery Status
-
Batterielaufzeit
4
{$SNMP_COMMUNITY}
1
.1.3.6.1.4.1.318.1.1.1.2.1.2.0
upsBasicBatteryTimeOnBattery
30
7
365
0
3
s
0
0
0
0
0.01
0
0
0
Verfügbarkeit
-
Batterieausgangsstatus
4
{$SNMP_COMMUNITY}
0
.1.3.6.1.4.1.318.1.1.1.4.1.1.0
upsBasicOutputStatus
60
7
365
0
3
0
0
0
0
1
0
0
0
Verfügbarkeit
APC upsBasicOutputStatus
-
Batterieladung
4
{$SNMP_COMMUNITY}
0
1.3.6.1.4.1.318.1.1.1.2.2.1.0
upsBatteryCharge
30
7
365
0
3
%
0
0
0
0
1
0
0
0
Verfügbarkeit
-
Batterietemperatur
4
{$SNMP_COMMUNITY}
1
.1.3.6.1.4.1.318.1.1.1.2.3.2.0
upsHighPrecBatteryTemperature
30
7
365
0
0
°C
0
0
0
0
0.1
0
0
0
Umgebung
-
Eingangsfrequenz
4
{$SNMP_COMMUNITY}
1
.1.3.6.1.4.1.318.1.1.1.3.3.4.0
upsHighPrecInputFrequency
30
90
365
0
0
Hz
0
0
0
0
0.1
0
0
0
Eingang
-
Eingangsspannung
4
{$SNMP_COMMUNITY}
1
1.3.6.1.4.1.318.1.1.1.3.3.1.0
upsHighPrecInputLineVoltage
30
90
365
0
0
V
0
0
0
0
0.1
0
0
0
Eingang
-
Ausgangslast (A)
4
{$SNMP_COMMUNITY}
1
.1.3.6.1.4.1.318.1.1.1.4.3.4.0
upsHighPrecOutputCurrent
30
90
365
0
0
A
0
0
0
0
0.1
0
0
0
Ausgang
-
Ausgangsfrequenz
4
{$SNMP_COMMUNITY}
1
1.3.6.1.4.1.318.1.1.1.4.3.2.0
upsHighPrecOutputFrequency
30
90
365
0
0
Hz
0
0
0
0
0.1
0
0
0
Ausgang
-
Ausgangsspannung
4
{$SNMP_COMMUNITY}
1
1.3.6.1.4.1.318.1.1.1.4.3.1.0
upsHighPrecOutputVoltage
30
90
365
0
0
V
0
0
0
0
0.1
0
0
0
Ausgang
{$SNMP_COMMUNITY}
public
{APC Smart-UPS SNMP Basic:upsAdvOutputLoad.last(0)}>90
Ausgangslast zu hoch
0
3
0
{APC Smart-UPS SNMP Basic:upsBatteryCharge.last(0)}<25
Battery Charge < 25%: {ITEM.LASTVALUE1}
0
4
0
{APC Smart-UPS SNMP Basic:upsBatteryCharge.last(0)}<50
Battery Charge < 50 %: {ITEM.LASTVALUE1}
0
5
0
Battery Charge < 25%: {ITEM.LASTVALUE1}
{APC Smart-UPS SNMP Basic:upsBatteryCharge.last(0)}<25
{APC Smart-UPS SNMP Basic:upsBatteryCharge.last(0)}<75
Battery Charge < 75%: {ITEM.LASTVALUE1}
0
2
0
Battery Charge < 50 %: {ITEM.LASTVALUE1}
{APC Smart-UPS SNMP Basic:upsBatteryCharge.last(0)}<50
{APC Smart-UPS SNMP Basic:upsHighPrecBatteryTemperature.last(0)}>40
High Battery Temperature
0
3
0
{APC Smart-UPS SNMP Basic:upsBasicOutputStatus.min(#3)}<>2
Loss of Input Power, current state - {ITEM.LASTVALUE1}
0
5
0
{APC Smart-UPS SNMP Basic:upsAdvReplaceBatteryIndicator.last(0)}<>1
Replace Battery
0
4
0
APC Battery Replacement Status
1
unknown
2
notInstalled
3
ok
4
failed
5
highTemperature
6
replaceImmediately
7
lowCapacity
APC Battery Status
1
unknown
2
batteryNormal
3
batteryLow
APC Kalibrierung
1
erfolgreich
2
fehlgeschlagen
3
läuft
APC upsBasicOutputStatus
1
unknown
2
onLine
3
onBattery
4
onSmartBoost
5
timedSleeping
6
softwareBypass
7
off
8
rebooting
9
switchedBypass
10
hardwareFailureBypass
11
sleepingUntilPowerReturn
12
onSmartTrim
13
ecoMode
14
hotStandby
15
onBatteryTest