3.0
2018-12-13T09:27:46Z
Templates USV
APC-Rack PDU-LLD SNMP
APC-Rack PDU-LLD SNMP
Templates USV
Generic
Power
-
Maximalleistung in A
1
public
0
.1.3.6.1.4.1.318.1.1.12.1.7.0
.1.3.6.1.4.1.318.1.1.12.1.7.0
86400
90
365
0
3
A
0
0
0
0
1
0
0
This OID will return the electrical rating of the device in Amps.
0
Power
-
Dosenanzahl
1
public
0
.1.3.6.1.4.1.318.1.1.12.1.8.0
.1.3.6.1.4.1.318.1.1.12.1.8.0
86400
90
365
0
3
0
0
0
0
1
0
0
This OID will return the number of outlets contained in the device.
0
Generic
-
Phasenanzahl
1
public
0
.1.3.6.1.4.1.318.1.1.12.1.9.0
.1.3.6.1.4.1.318.1.1.12.1.9.0
86400
90
365
0
3
0
0
0
0
1
0
0
This OID will return the number of phases supported by the device.
0
Generic
-
Leistung in Watt
1
public
0
.1.3.6.1.4.1.318.1.1.12.1.16.0
.1.3.6.1.4.1.318.1.1.12.1.16.0
30
90
365
0
3
W
0
0
0
0
1
0
0
This OID will return the Power in Watts.
0
Power
-
Leistung in VA
1
public
0
.1.3.6.1.4.1.318.1.1.12.1.18.0
.1.3.6.1.4.1.318.1.1.12.1.18.0
30
90
365
0
3
VA
0
0
0
0
1
0
0
This OID will return the Power in VA.
0
Power
-
Supply 1 Status
1
public
0
1.3.6.1.4.1.318.1.1.12.4.1.1.0
apc.pdu.supply.1.state
30
90
365
0
3
0
0
0
0
1
0
0
0
Power
Cisco-Interface state
-
Supply 2 Status
1
public
0
1.3.6.1.4.1.318.1.1.12.4.1.2.0
apc.pdu.supply.2.state
30
90
365
0
3
0
0
0
0
1
0
0
0
Power
Cisco-Interface state
-
Spannung (line to line)
1
public
0
1.3.6.1.4.1.318.1.1.12.1.15.0
apc.pdu.voltage
30
90
365
0
3
V
0
0
0
0
1
0
0
0
Power
-
Power Feed
15
0
powerFeed
120
7
365
0
3
A
0
0
0
0
1
{$MAX_FEED}
0
0
Maximum load on the powerfeed the powerswitch has been connected to.
0
Power
-
Power Usage
4
{$SNMP_COMMUNITY}
1
SNMPv2-SMI::enterprises.318.1.1.12.2.3.1.1.2.1
powerUsage
120
7
365
0
0
A
0
0
0
0
0.1
0
0
0
Power
-
Low Load Warning Threshold
4
{$SNMP_COMMUNITY}
0
SNMPv2-SMI::enterprises.318.1.1.12.2.2.1.1.2.1
thresholdLow
1800
7
365
0
3
A
0
0
0
0
1
0
0
0
Power
-
Near Overload Warning Threshold
4
{$SNMP_COMMUNITY}
0
SNMPv2-SMI::enterprises.318.1.1.12.2.2.1.1.3.1
thresholdNear
1800
7
365
0
3
A
0
0
0
0
1
0
0
0
Power
-
Overload Alarm Threshold
4
{$SNMP_COMMUNITY}
0
SNMPv2-SMI::enterprises.318.1.1.12.2.2.1.1.4.1
thresholdOverload
1800
7
365
0
3
A
0
0
0
0
1
0
0
0
Power
Outlet Discovery
1
{$SNMP_COMMUNITY}
discovery[{#SNMPVALUE},SNMPv2-SMI::enterprises.318.1.1.12.3.3.1.1.2]
outlet.discovery
300
0
0
0
0
0
0
30
discovers the amount of outlets of the APC.
Description for port {#SNMPINDEX}
4
{$SNMP_COMMUNITY}
0
SNMPv2-SMI::enterprises.318.1.1.12.3.3.1.1.2.{#SNMPINDEX}
portdescr[{#SNMPINDEX}]
3600
90
0
0
1
0
0
0
0
1
0
0
0
Power
Status for port {#SNMPINDEX}
1
public
0
.1.3.6.1.4.1.318.1.1.12.3.3.1.1.4.{#SNMPINDEX}
portstatus[{#SNMPINDEX}]
120
90
365
0
3
0
0
0
0
1
0
0
0
Power
APC Port Status
Phase for port {#SNMPINDEX}
1
public
0
1.3.6.1.4.1.318.1.1.12.3.5.1.1.3.{#SNMPINDEX}
snmp.discovery.pdu.outlets.phase.[{#SNMPINDEX}]
30
90
365
0
3
0
0
0
0
1
0
0
0
Generic
Status "[{#SNMPVALUE}]"
1
public
0
1.3.6.1.4.1.318.1.1.12.3.5.1.1.4.{#SNMPINDEX}
snmp.discovery.pdu.outlets.status.[{#SNMPINDEX}]
30
90
365
0
3
0
0
0
0
1
0
0
0
APC Port Status
{APC-Rack PDU-LLD SNMP:portstatus[{#SNMPINDEX}].last(0)}=2 and {APC-Rack PDU-LLD SNMP:portstatus[{#SNMPINDEX}].change(0)}=1
Port {#SNMPINDEX} on {HOSTNAME} has been powered off ({#SNMPVALUE})
http://{HOST.CONN}/
0
2
0
{APC-Rack PDU-LLD SNMP:portstatus[{#SNMPINDEX}].last(0)}=1 and {APC-Rack PDU-LLD SNMP:portstatus[{#SNMPINDEX}].change(0)}=1
Port {#SNMPINDEX} on {HOSTNAME} has been powered on ({#SNMPVALUE})
http://{HOST.CONN}/
0
1
0
{APC-Rack PDU-LLD SNMP:portstatus[{#SNMPINDEX}].last(0)}=4
Port {#SNMPINDEX} on {HOSTNAME} is in error state ({#SNMPVALUE})
http://{HOST.CONN}/
0
4
The power outlet is faulty, please investigate.
0
{APC-Rack PDU-LLD SNMP:portstatus[{#SNMPINDEX}].last(0)}=3 and {APC-Rack PDU-LLD SNMP:portstatus[{#SNMPINDEX}].change(0)}=1
Port {#SNMPINDEX} on {HOSTNAME} is rebooting ({#SNMPVALUE})
http://{HOST.CONN}/
0
2
0
Port status ({#SNMPVALUE})
900
200
0.0000
5.0000
1
1
0
1
0
0.0000
0.0000
0
1
0
0
0
5
EE00EE
0
7
0
-
APC-Rack PDU-LLD SNMP
portstatus[{#SNMPINDEX}]
{$MAX_FEED}
16
{$SNMP_COMMUNITY}
public
{APC-Rack PDU-LLD SNMP:powerUsage.last(0)}>{APC-Rack PDU-LLD SNMP:thresholdNear.last(0)}
Powerusage on {HOSTNAME} is nearly overloaded
http://{HOST.CONN}/
0
2
0
Power usage on {HOSTNAME} is overloaded
{APC-Rack PDU-LLD SNMP:powerUsage.last(0)}>{APC-Rack PDU-LLD SNMP:thresholdOverload.last(0)}
{APC-Rack PDU-LLD SNMP:powerUsage.last(0)}>{APC-Rack PDU-LLD SNMP:thresholdOverload.last(0)}
Power usage on {HOSTNAME} is overloaded
http://{HOST.CONN}/
0
2
0
{APC-Rack PDU-LLD SNMP:powerUsage.max(300)}={APC-Rack PDU-LLD SNMP:thresholdLow.last(0)}
Power usage on {HOSTNAME} is too low
http://{HOST.CONN}/
0
3
The power usage has reached the Low threshold.
0
Power usage
900
200
0.0000
100.0000
1
1
0
1
0
0.0000
0.0000
1
2
0
APC-Rack PDU-LLD SNMP
powerFeed
0
1
EEEE00
0
4
0
-
APC-Rack PDU-LLD SNMP
powerUsage
1
4
E56717
0
1
0
-
APC-Rack PDU-LLD SNMP
thresholdNear
2
4
DD0000
0
1
0
-
APC-Rack PDU-LLD SNMP
thresholdOverload
APC Port Status
1
On
2
Off
3
Rebooting
4
Error
Cisco-Interface state
1
up
2